Home

NEMA/IP

Military Standards

NEC

UL/CSA/CE

Moisture Removal

Mounting

NEMA

NEMA- 12
Type 12 enclosures are intended for indoor use primarily to provide a degree of protection against dust, falling dirt, and dripping non-corrosive liquids.
Applies to AHP- FF & FHP models

NEMA- 4X
Type 4X enclosures are intended for indoor and outdoor use primarily to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose directed water TECA products carrying the "X" designation use Mil-Spec fans, o-ring sealed power supplies, no exposed electronic components, stud/gasket mounting and Mil-Spec finishes. Products with the "XE" designation use sealed fans, sealed components, stud/gasket mounting and Mil- Spec finishes. They are designed to maintain the enclosure rating and perform in the rated environment.
Applies to AHP- X, AHP-XE & FHP-XE models

Source: NEMA Publication N0. 250, Part 1, Page 1

 

IP Ratings

The IP (Ingress Protection) standard describes a uniform system for classifying the degrees of protection provided by the enclosures of electrical equipment. The first number refers to the level of protection against penetration of solid objects into the enclosure. The second number refers to the level of protection against penetration of liquids into the enclosure.

Number

Level of protection

Number

Level of Protection

0

No protection

0

No protection

1

Protection against objects over 50mm, accidental touch by hands

1

Protection against vertically dripping water

2

Protection against objects over 12mm, protection against touch by fingers

2

Protection against liquid drops at 15° from vertical

3

Protection against objects over 2.5mm, tools, wires, etc.

3

Protection against rain at angle of up to 60° from vertical

4

Protection against objects over 1mm, small tools, wires, etc.

4

Protection against splash from any direction

5

Complete protection against contact. Protection against harmful ingress and deposit of dust

5

Protection against water jets from any direction

6

Complete protection against contact. Protection against ingress of dust

6

Protection against heavy sea water

 

 

7

Protection against immersion in water under stated conditions of pressure and time

 

 

8

Protection under indefinite immersion in water under specified pressure

Source: Hoffman® standards, page A.05

 

NEMA & IP Ratings Comparison

Enclosure NEMA    Rating

IP Rating

1

10

2

11

3

54

4

56

4X

66

6

67

12

52

13

54

Note: The comparison chart above is only an approximation.

 