Reliability

 

TECA Model AHP1200XHC

MTBF calculation was made using Telcordia SR-332, Method II.

Mean time between failures prediction ranges from 80,000 hours for ground benign, outdoor, 25C environment to 47,700 hours for ground mobile, outdoor, 70C environment.

On this website under "APPLICATIONS", please also see the ongoing test of TECA Model AHP1800XEHC which has been in continuous service for over 45,000 hours outdoors on the roof. There is also a picture and description of a TECA Model AHP1200X with 120,000 hours of duty with no problems other than dirt!

 

 

Using:  Telcordia SR332, Method 2-TELCORDIA2 Prediction Date:  10 Jan 2006
Temperature:  40.00     Environment:  GF  
         
Part   Style QTY F/R (FPMH) MTBF (hours)
Thermostat   NPRD - Data 3 2.531200                    131,690
1   Heater 2 1.900000                    263,158
2   Thermal Overcurrent Circuit Breakers 1 0.399000                2,506,266
3   Tubeaxial Fan 1 0.200000                5,000,000
4   Tubeaxial Fan 1 0.200000                5,000,000
5   Thermoelectric Module 12 0.099005                    841,706
6   Solid State Relay 2 0.050000              10,000,000
7   Bridge Rectifier 1 0.013438              74,418,051
8   Metal Oxide Varisor 1 0.010078              99,224,068
9   Power Resistor 1 0.005322            187,916,234
10   Generic Coil 1 0.001000        1,000,000,000
11   Generic Ceramic Capacitor 1 0.000881        1,135,250,317
12   Polypropylene Capacitor 1 0.000615        1,627,185,717
13   Input Filter 1 0.005295            188,875,248
AHP-1200HXC   Air Conditioner 1 13.517291               73,979

 

 

 