AHP-XP & AHP-CXP Series Air Conditioners
Thru mount, Class 1, Division 2,
NEMA-4X Solid state air
conditioners
Thru mount, Class 1, Division 1, NEMA-4X Solid state air
conditioners
|
|
TECA’s XP-Series thermoelectric air
conditioners are designed for rugged Nema-4X (IP56) locations as well as
hazardous duty installations including Class I, Division 2, groups
A-D. They can withstand corrosive salt spray, windblown dust,
rain and water hose down from any angle in outdoor or indoor
locations. A stud and gasket style mount is provided to maintain
your enclosures integrity. Military fans are employed on the
exterior for long life and durability. |
|

AHP-1200XP
530-670 BTU/hr rating, 15" x 7.3" mounting area, 120, 240 VAC
operation
Class 1 Division 2, Nema-4X (IP56), UL-1604 |
|

AHP-1800XP
1100-1420 BTU/hr rating, 18" x 12.3" mounting area,
120 and
120/240 VAC operation
Class 1 Division 2,
Nema-4X (IP56), UL-1604 |
|

AHP-1200CXP
307-680 BTU/hr rating, 15" x 7.3" mounting area, 120 VAC
operation
Class 1 Division 1, Groups B, C, D, Nema-4X
Group II, Catagory 2 [1] G, EExd [ia] ia IIB+H2 T4 |
|

AHP-X and XE Series
The world 's most widely used solid state air conditioner for
NEMA-4 and NEMA-4X style enclosures.
Agency approved versions available. |
|
CID2 Class I, Division 2 (Hazardous
Environments) – a location (1) in which volatile flammable liquids
or flammable gases are handled, processed, or used, but in which the liquids,
vapors, or gases will normally be confined within closed containers
or closed systems from which they can escape only case of
accidental rupture or breakdown such containers or systems, or in
case of abnormal operation of equipment; or (2) in which ignitable
concentrations of gases or vapors are normally prevented by
positive mechanical ventilation, and which might become hazardous
through failure or abnormal operation of the ventilating
equipment; or (3) that is adjacent to a Class I, Division 1 location,
and to which ignitable concentrations gases or vapors might
occasionally be communicated unless such communication is
prevented by adequate positive-pressure ventilation from a source
of clean air, and effective safeguards against ventilation failure
are provided.
Source: NEC 2005, Article 500
Groups (A-D) Atmospheres containing the following:
acetylene, hydrogen, fuel, and combustible process gases containing
more than 30% hydrogen by volume, or gases or vapors of equivalent
hazard such as butadiene, ethylene oxide, propylene oxide,
acrolein, ethyl ether, ethylene, or gases or vapors of equivalent
hazard such as acetone, ammonia, benzene, butane cyclopropoane,
ethanol, gas-line, hexane, methanol, methane, natural gas,
naphtha, propane, or gases or vapors of equivalent hazard.
Applies to XP models.
Source: NEC 2005, Article 500
C1D1 Groups B, C, D Class 1, Division 1 (Hazardous
Environments) - As an integral part of a larger systems
AHP-1200CXP has been investigated in accordance with UL
3111-1, First Edition, rev. 6/94 Electrical Equipment for
laboratory use and CSA C22.2 No. 1010.1-92 - Safety requirements
for Electrical Equipment for Measurement, Control, and Laboratory
use.
As an integral part of a larger system it has been investigated in
accordance with NFPA 496 Edition - Purged and pressurized
Enclosure for Electrical Equipment.
|
|